TECHNICAL CHARACTERISTICS
| Description | Value |
|---|---|
| Product range | Modicon X80 |
| Product or component type | Power supply module |
| Backplane compatibility | Not compatible with BMEXBP…02 |
| Primary voltage | 100…240 V |
| Power supply circuit type | AC |
| Secondary power |
10.8 W 24 V DC – sensor power supply 16.8 W 24 V DC – processor and I/O module 8.3 W 3.3 V DC – logical I/O module power supply |
| Primary voltage limits | 85…264 V |
| Network frequency | 50/60 Hz |
| Network frequency limits | 47…63 Hz |
| Apparent power | 0.07 kVA |
| Input current |
0.31 A at 240 V 0.61 A at 115 V |
| Inrush current |
30 A at 120 V 60 A at 240 V |
| I²t at switch-on | 12 A².s at 240 V |
| It at switch-on |
0.06 As at 240 V 0.03 As at 120 V |
| MTBF reliability | 4,638,000 h |
| Protection type |
Non-accessible internal fuse – primary circuit Overload protection – secondary circuit Overvoltage protection – secondary circuit Short-circuit protection – secondary circuit |
| Secondary voltage current |
0.45 A 24 V DC – sensor 0.7 A 24 V DC – processor and I/O module 2.5 A 3.3 V DC – logical I/O module |
| Maximum power dissipation | 8.5 W |
| LED status |
1 LED (green) – rack voltage OK 1 LED (green) – sensor voltage |
| Control type | RESET push-button – cold restart |
| Electrical connection |
1 2-pin connector – alarm relay 1 5-pin connector – line power supply, earth, 24 V DC sensor |
| Insulation resistance |
≥ 100 MΩ primary / ground ≥ 100 MΩ primary / secondary |
| Product weight | 0.3 kg |
| Micro-break immunity | 1 ms |
| Dielectric strength |
1500 V primary / secondary – logical I/O module 1500 V primary / secondary – processor and I/O module 2300 V primary / secondary – sensor power supply 1500 V primary / ground 500 V 24 V sensor output / ground |
| Vibration resistance | 3 gn |
| Mechanical shock resistance | 30 gn |
| Degree of protection | IP20 |
| European directives |
2014/35/EU – Low Voltage Directive 2014/30/EU – Electromagnetic Compatibility |
| Storage temperature | -40…85 °C |
| Operating temperature | 0…60 °C |
| Relative humidity | 5…95 % at 55 °C without condensation |
| Protective treatment | TC |
| Operating altitude |
0…2000 m 2000…4000 m with derating factor |
| Packaging – Type 1 | PCE – 1 unit – 13.5 × 15.4 × 16.4 cm – 481 g |
| Packaging – Type 2 | S04 – 12 units – 30 × 40 × 60 cm – 6.438 kg |
| Packaging – Type 3 | P06 – 48 units – 75 × 60 × 80 cm – 35.804 kg |